Type TR01-6A TR01-12A TR01-24A
Suitable for transformer capacity 1 @ 25 kVA 1 @ 50 kVA 1 @ 100 kVA
Max. system voltage 8.3 kV
Rating voltage 6.9 KV
Rating current 25 A
BIL 125 kV Test report No.tertec 94165
AC withstand voltage 40 KV 1 min. Test report No.tertec 94165
Interrupting current 2200 A (sym); 3500 A (Asym) Test report No.tertec 94165
Short circuit current 1000 A (sym) 2 times Test report No.KERI 2005TC00196
Magnetizing current 250 mA Test report No.KERI 2005C00196
Operating temperature 0°C~140°C
The rate of temperature shift 0.7%/°C
TCC tolerance 10%
Mechanic operation Operation at least 1,000 times
Full range current limiting fuse Type JAKER TRO2-20C JAKER TR02-40C-F JAKER TR02-40C-N
Impedance voltage Z% ≥ 1.1% 7% ≥1.3%. 7% ≥1.9%